Sept 2, 2008 New Store Hours
8 AM to 6 PM Eastern Time
Monday through Friday
The new Lev-UPS™ Pro models are an expansion and improvement of the previous Leviton Tower line of uninterruptible power supplies. Pro models provide up-to-the-minute sine-wave tracking and control firmware to improve response time and efficiency.
A line-interactive design featuring tap-changing Lev-CON™ Automatic Voltage Regulation technology provides mitigation of sags and swells without relying on backup battery power. This conserves battery energy for more severe disturbances such as power interruptions and outages.
All models come with Leviton's "Lev-WARE™" power-monitoring & UPS-control software at no additional cost. The unique energy saving "Sleep Mode" reduces the cost of ownership and the "Cold Start" feature allows the UPS to be used as a small emergency power source.
A variety of programmable alarms and indicators provide users with information on system status as well as AC and communication line surge protection. Also unique to Leviton are dry contacts via a standard RS-232 DB-9 connection that allow for remote signaling of basic functions such as Power Normal, Backup Mode & Low Battery states.
They are ideal for the more discerning consumer as well as for general commercial and industrial applications.
| Model | ||||||
|---|---|---|---|---|---|---|
| U0425-AKP | U0625-AKP | U1000-AKP | U1500-AKP | U2200-AKP | ||
| Input | Capacity | 425VA/255W | 625VA/375W | 1000VA/600W | 1500VA/900W | 2200VA/1320W |
| Voltage | 120V +/-25% | |||||
| Frequency | 50 or 60Hz +/-5% (auto sensing) | |||||
| Output | Voltage (on battery) |
120V +/-5% Simulated sine wave output | ||||
| Frequency (on battery) |
50 or 60Hz +/-0.5% | |||||
| Voltage regulation LEV-CON™ |
This automatically increases the output voltage 15% above input voltage if it's-9% to -25% below nominal. It decreases the output voltage 15% below input voltage if it's +9% to +25% above nominal. | |||||
| Transfer Time | 2/4 milliseconds, including detection time | |||||
| Protection and Filtering | Transient Protection | Response time: < 5nsec. Tested to ANSI/IEEE C62.45 performance evaluation standards. Wave forms – Per IEEE C62.41: Normal mode – 6kV 1.2/50μseconds, 500A 8/20μseconds, combination wave. Common mode – Category A & B ring wave tr = 0.5useconds, 100kHz | ||||
| EMI/RFI Filter | 10dB at 0.15MHz, 50dB at 30MHz | |||||
| Overload Protection | Automatic UPS shutdown if overload exceeds 110% of nominal for 60 seconds and 130% for 3 seconds. | |||||
| 10Base-T port | Network (UTP, RJ-45) compatible jacks. | |||||
| Unit Input | Fuse for overload & short circuit protection | |||||
| Short Circuit | UPS output is cut-off immediately or input fuse blows. | |||||
| Battery | Type | Sealed, maintenance-free, lead acid | ||||
| Recharge Time | 4 hours typically (to 90% of full capacity) | |||||
| Protection | Automatic self-test & discharge protection. Battery replacement indicator | |||||
| Back-Up Time | 5 to 60 minutes (depending on load) | |||||
| Physical | Net Weight lbs (kg) |
12.8 (5.8) | 14.3 (6.5) | 33 (15) | 40 (16.8) | 57 (26) |
| Ship Weight lbs (kg) |
13.5 (6.2) | 15.2 (6.9) | 35.6 (16.2) | 34.3 (15.6) | 62 ((28.2) | |
| Dimensions ins (mm) WxDxH |
3.8x12.6x5.3 (97x320x135) | 3.8x12.6x5.3 (97x320x135) | 5.1x15x7.5 (130x382x195) | 5.1x15x7.7 (130x382x195) | 6.7x17x8.7(170x448x221) | |
| Input Receptacle | IEC 320 type | |||||
| No. of Output Receptacles | Two (2) NEMA 5-15R | Two (2) NEMA 5-15R | Five (5) NEMA 5-15R | Five (5) NEMA 5-15R | Six (6) NEMA 5-15R | |
| Alarms | Battery Back-Up | Slow beeping sound (approx. 0.47Hz) | ||||
| Battery Low | Rapid beeping sound (approx. 1.824Hz) | |||||
| Overload | Continuous beeping sound | |||||
| Communication | DB9 Interface | RS-232 connection Bi-directional communication port & dry contact signaling | ||||
| Safety Agency | Approvals | UL1778, CUL, meets FCC, Class A requirements | ||||
| Environment | Ambient | 18,000 ft. max. elevation, 0-95% humidity non-condensing 32-104°F (0-40°C) | ||||
| Audible Noise | <48dBA (1 meter from surface) | |||||
| Storage | 45000 ft max. elevation | |||||
| Load VA/Watts | U0425-AKP 425VA/255W | U0625-AKP 625VA/375W | U1000-AKP 1000VA/600W | U1500-AKP 1500VA/900W | U2200-AKP 2200VA/1320W |
|---|---|---|---|---|---|
| 75/45 | 78 | 70 | 80 | 118 | 246 |
| 150/90 | 27 | 28 | 55 | 73 | 126 |
| 300/180 | 10 | 13 | 32 | 38 | 75 |
| 425/255 | 4 | 9 | 20 | 25 | 52 |
| 500/300 | — | 6 | 13 | 21 | 42 |
| 625/375 | — | 4 | 7 | 19 | 29 |
| 1000/600 | — | — | 4 | 17 | 24 |
| 1200/720 | — | — | — | 12 | 19 |
| 1500/900 | — | — | — | 5 | 14 |
| 1800/1080 | — | — | — | — | 9 |
| 2200/1320 | — | — | — | — | 5 |
| Part # | Description | Lashen's Price |
|---|---|---|
| U0500-AKP | Line Interactive UPS Uninterruptable Pwr Supply, 500VA / 300W at 120 Volt +/- 5 Percent Simulated Sine Wave Output, With LED Diagnostics in Shelf Mount Enclosure - Beige | $355.65 each |
| U1000-AKP | Line Interactive UPS Uninterruptable Pwr Supply, 1000VA / 600W at 120 Volt +/- 5 Percent Simulated Sine Wave Output, With LED Diagnostics in Tower Enclosure - Beige | $316.88 each |
| U1500-AKP | Line Interactive UPS Uninterruptable Pwr Supply, 1500VA / 1050W at 120 Volt +/- 5 Percent Simulated Sine Wave Output, With LED Diagnostics in Tower Enclosure - Beige | $406.88 each |
| U2200-AKP | Line Interactive UPS Uninterruptable Pwr Supply, 2200VA / 1320W at 120 Volt +/- 5 Percent Simulated Sine Wave Output, With LED Diagnostics in Tower Enclosure - Beige | $641.25 each |